Contact us 800.813.8448

Recently added item(s) ×

You have no items in your shopping cart.

EM Test Compact NX5 BSP-1-300-16; Burst, Surge, Power Fail

Model Number: NX5 BSP-1-300-16

EM Test Compact NX5 BSP-1-300-16; Burst, Surge, Power Fail

Click on above image to view full picture

Condition

Refurbished

Availability
  • Quote to Rent/Lease
Description

EM Test Compact NX5 BSP-1-300-16

Available for rent

This simulator includes SURGE, EFT, and INTERRUPTS

Modular Ultra Compact Simulator configured with EFT to 5.5kV, SURGE to 5kV and fast switch (under 5µs) for INTERRUPTS per IEC 61000-4-11. Ready to accept optional external transformer or variac to perform the DIPS portion of -11. Includes:

  • Internal Single Phase CDN 300V AC/DC; 16A
  • Monitor Ports for Both Peak Impulse & EUT Power
  • USB and Ethernet interfaces
  • iec.control SOFTWARE Included – Control Only

The compact NX5 is the most economical solution for fully compliant immunity tests and CE marking. A built-in CDN is used for testing single-phase EUTs, while tests on three-phase EUTs can be performed by adding a fully controlled external coupling network up to 200 A. EM TEST supplies a wide range of accessories for nearly all test procedures and applications.

Video

Test Standards
  •  EN 61000-4-11
  •   EN 61000-4-4: 2012
  •   EN 61000-4-5
Specifications
Burst
  • Test voltage: 200 V–5,500 V ± 10%; 100 V–2,750 V ± 10% at 50 Ω load
  • Pulse shape: 5/50 ns at 50 Ω and 1,000 Ω
  • Pulse triggering: Automatic, manual, external
  • Polarity: Positive/negative/alternating
  • Synchronization: 0°–360°, resolution 1° (16-500Hz)
  • Output/Direct: Via 50 Ω coaxial
Surge
  • Voltage (o.c.): 160 V–5,000 V ± 10%
  • Current: (s.c.) Max. 2,500 A ± 10%
  • Rise time: 1.2 μs ± 30%
  • Decay time to half value: 50 μs ± 20%
  • Rise time: 8 μs ± 20%
  • Decay time to half value: 20 μs ± 20%
  • Pulse triggering: Automatic, manual, external
  • Polarity: Positive/negative/alternating
  • Synchronization: 0°–360°, resolution 1°, asynchronous
  • Repetition rate: Max. 1 Hz (1 s–9,999 s)
  • Output/Direct: Via HV connectors to external coupling network
Power-Fail
  • Channel: PF1/PF2 Voltage: max. 300 V AC / DC, Current: max. 16 A AC / DC
  • Frequency: 16 Hz–500 Hz and DC
  • Switching time :< 5 μs at 100 Ω resistive load
  • Inrush current: > 500 A
  • Trigger: Automatic, manual, external
  • Synchronization: 0°–360°, resolution 1°, (16–500 Hz), asynchronous
  • Output EUT terminals/ Trigger: L, N and PE, 5 V trigger signal for oscilloscope
Standard Accessories Included
  • Mains Supply
  • EUT Supply
  • EUT Adapter
  • Operation Manual
  • Calibration Certificate
  • iec.control remote software
$0.00

Request a Quote