Test voltage
- OTS 60PB -30 to +30 kVrms
- Voltage resolution 0.1 kV, ±1%, ±2 digits
Oil temperature measuring range 10 ºC to 65 ºC
Oil temperature sensor resolution 1 ºC
Power supply Line voltage 85 to 265 VAC Line frequency 50/60 Hz
Batteries (option) Lead acid 2 x 12 V 4 Ah, or NiMH 24 V 2 Ah
Interfaces USB 2.0 compatible 2 x USB type-A (memory stick) 1 x USB type-B (printer or PC)
External printer Any printer with USB interface and PCL3 driver
Protection Safety interlock on cover
Display 320 x 240 QVGA colour display with backlight
Dimensions
- OTS 60PB 520 mm x 340 mm x 250 mm
Weight
- OTS 60PB 16 kg (printer, no battery), 16.8 kg (printer, NiMH battery)
Environmental
- Operating temperature 0 ºC to +50 ºC
- Storage temperature -30 ºC to +65 ºC
- Humidity 80% RH at 40 ºC operation 95% RH at 40 ºC storage
Safety
- Designed in accordance with IEC61010
EMC
- Light industrial IEC 61326-1 Class B, CISPR 22, CISPR 16-1 and CISPR 16-2